EXPERIMENTAL SUBSTANTIATION OF THE CALCULATION PROCEDURE OF NORMALIZED PARAMETERS OF GROUNDING DEVICE BASED ON THE THREE-LAYER SOIL MODEL

Purpose. Experimental substantiation of the possibility of using the calculation procedure of normalized parameters grounding devices on the basis of a three-layer model soil. Methodology. The research was based on comparison of the results of experimental measurements for the existing high voltage...

Повний опис

Збережено в:
Бібліографічні деталі
Дата:2018
Автори: Koliushko, D. G., Rudenko, S. S.
Формат: Стаття
Мова:English
Ukrainian
Опубліковано: National Technical University "Kharkiv Polytechnic Institute" and State Institution “Institute of Technical Problems of Magnetism of the National Academy of Sciences of Ukraine” 2018
Теми:
Онлайн доступ:http://eie.khpi.edu.ua/article/view/2074-272X.2018.1.11
Теги: Додати тег
Немає тегів, Будьте першим, хто поставить тег для цього запису!
Назва журналу:Electrical Engineering & Electromechanics

Репозитарії

Electrical Engineering & Electromechanics
Опис
Резюме:Purpose. Experimental substantiation of the possibility of using the calculation procedure of normalized parameters grounding devices on the basis of a three-layer model soil. Methodology. The research was based on comparison of the results of experimental measurements for the existing high voltage energy facilities of Ukraine with the results of the calculation. Results. Comparison showed that the average error decreased from 18 % for the two-layer model to 10 % for the three-layer model. The analysis of the calculated and experimentally determined values of the touch voltage showed a high degree of coincidence. Originality. The adequacy of the calculation procedure of the normalized parameters of the grounding device for model with three-layer soil is substantiated by the results of experimental research on the existing energy objects. Practical value. The obtained results allow us to use calculation procedure to create software to determine with increased accuracy the normalized parameters of grounding device located in three-layer soils.