Decrease in the damage of powerful turbogenerator stator caused by vibration in the end zones (analysis, hypotheses, experiment)
The analysis of the turbogenerators’ TВВ-1000-2Y3 failure has shown that the most vulnerable link in the stator is such of their elements as tightening prisms, the teeth of the end packet core, lead-out and connecting buses of the stator winding. The basic reason for the destruction of the elements...
Gespeichert in:
| Datum: | 2014 |
|---|---|
| Hauptverfasser: | , |
| Format: | Artikel |
| Sprache: | Russian |
| Veröffentlicht: |
National Technical University "Kharkiv Polytechnic Institute" and Аnatolii Pidhornyi Institute of Power Machines and Systems of NAS of Ukraine
2014
|
| Schlagworte: | |
| Online Zugang: | http://eie.khpi.edu.ua/article/view/2074-272X.2014.1.07 |
| Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
| Назва журналу: | Electrical Engineering & Electromechanics |
Institution
Electrical Engineering & Electromechanics| Zusammenfassung: | The analysis of the turbogenerators’ TВВ-1000-2Y3 failure has shown that the most vulnerable link in the stator is such of their elements as tightening prisms, the teeth of the end packet core, lead-out and connecting buses of the stator winding. The basic reason for the destruction of the elements mentioned is metal fatigue caused by excessive vibration under the influence of variable axial forces of electromagnetic origin. Preventing the destruction of the structural elements may be achieved by vibration monitoring and diagnostics. |
|---|