Power quality enhancement using active power filter five-level cascade H-bridge under unbalanced and distorted grid

Introduction. To improve the power quality of a supply system, the total harmonic distortion (THD) is the most important parameter in the quantification of harmonics caused by nonlinear loads. In practice, it must be less than 5 %. The novelty of the proposed work consists in the use of a cascaded f...

Повний опис

Збережено в:
Бібліографічні деталі
Дата:2023
Автори: Guergah, M., Nebti, K., Rezgui, S. E., Benalla, H., Ould-Abdeslam, D.
Формат: Стаття
Мова:English
Опубліковано: National Technical University "Kharkiv Polytechnic Institute" and State Institution “Institute of Technical Problems of Magnetism of the National Academy of Sciences of Ukraine” 2023
Теми:
Онлайн доступ:http://eie.khpi.edu.ua/article/view/257421
Теги: Додати тег
Немає тегів, Будьте першим, хто поставить тег для цього запису!
Назва журналу:Electrical Engineering & Electromechanics

Репозитарії

Electrical Engineering & Electromechanics
id eiekhpieduua-article-257421
record_format ojs
institution Electrical Engineering & Electromechanics
collection OJS
language English
topic multilevel active power filter
total harmonic distortion
instantaneous active and reactive power
harmonic currents
synchronous reference frame theory
багаторівневий фільтр активної потужності
повні гармонічні спотворення
миттєва активна та реактивна потужності
гармонічні струми
синхронна теорія системи відліку
spellingShingle multilevel active power filter
total harmonic distortion
instantaneous active and reactive power
harmonic currents
synchronous reference frame theory
багаторівневий фільтр активної потужності
повні гармонічні спотворення
миттєва активна та реактивна потужності
гармонічні струми
синхронна теорія системи відліку
Guergah, M.
Nebti, K.
Rezgui, S. E.
Benalla, H.
Ould-Abdeslam, D.
Power quality enhancement using active power filter five-level cascade H-bridge under unbalanced and distorted grid
topic_facet multilevel active power filter
total harmonic distortion
instantaneous active and reactive power
harmonic currents
synchronous reference frame theory
багаторівневий фільтр активної потужності
повні гармонічні спотворення
миттєва активна та реактивна потужності
гармонічні струми
синхронна теорія системи відліку
format Article
author Guergah, M.
Nebti, K.
Rezgui, S. E.
Benalla, H.
Ould-Abdeslam, D.
author_facet Guergah, M.
Nebti, K.
Rezgui, S. E.
Benalla, H.
Ould-Abdeslam, D.
author_sort Guergah, M.
title Power quality enhancement using active power filter five-level cascade H-bridge under unbalanced and distorted grid
title_short Power quality enhancement using active power filter five-level cascade H-bridge under unbalanced and distorted grid
title_full Power quality enhancement using active power filter five-level cascade H-bridge under unbalanced and distorted grid
title_fullStr Power quality enhancement using active power filter five-level cascade H-bridge under unbalanced and distorted grid
title_full_unstemmed Power quality enhancement using active power filter five-level cascade H-bridge under unbalanced and distorted grid
title_sort power quality enhancement using active power filter five-level cascade h-bridge under unbalanced and distorted grid
title_alt Power quality enhancement using active power filter five-level cascade H-bridge under unbalanced and distorted grid
description Introduction. To improve the power quality of a supply system, the total harmonic distortion (THD) is the most important parameter in the quantification of harmonics caused by nonlinear loads. In practice, it must be less than 5 %. The novelty of the proposed work consists in the use of a cascaded five level active filter, when the converter consisting of six H-bridge pairs, each one includes four transistors. Purpose. To increase the efficiency of this filter, two techniques for quantification of harmonic currents are proposed, first the PQ-theory which is simple but can only be used in case of a balanced grid, and second the synchronous reference frame theory (SFR-theory), which is capable of creating harmonic current not only in an unbalanced grid, but also in an unbalanced and distorted beam. Methods. Using the control techniques, the harmonic current is extracted from load current and considered as a reference. The constructed current should follow this reference. Results. The estimation of the active and reactive powers is based on the measurement of the currents crossing the load and the network voltages, these powers are used to determine the shape of the harmonic (reference) current. Using the PI regulator, the output current of the five-level inverter follows the reference current perfectly. The inverters output current is injected into the grid to eliminate harmonic currents. Practical value. In practice, the harmonic distortion rate THD is the most widely used criterion for criticizing the waveform of the currents and judging the quality of the energy involved. For currents on the source side, the THD is considered acceptable if it is less than 5 %, in our proposal the THD is 0.85 % with the PQ-theory and 2.34 % with SFR-theory, so it is optimal.
publisher National Technical University "Kharkiv Polytechnic Institute" and State Institution “Institute of Technical Problems of Magnetism of the National Academy of Sciences of Ukraine”
publishDate 2023
url http://eie.khpi.edu.ua/article/view/257421
work_keys_str_mv AT guergahm powerqualityenhancementusingactivepowerfilterfivelevelcascadehbridgeunderunbalancedanddistortedgrid
AT nebtik powerqualityenhancementusingactivepowerfilterfivelevelcascadehbridgeunderunbalancedanddistortedgrid
AT rezguise powerqualityenhancementusingactivepowerfilterfivelevelcascadehbridgeunderunbalancedanddistortedgrid
AT benallah powerqualityenhancementusingactivepowerfilterfivelevelcascadehbridgeunderunbalancedanddistortedgrid
AT ouldabdeslamd powerqualityenhancementusingactivepowerfilterfivelevelcascadehbridgeunderunbalancedanddistortedgrid
first_indexed 2024-06-01T14:40:12Z
last_indexed 2024-06-01T14:40:12Z
_version_ 1800670085445058560
spelling eiekhpieduua-article-2574212023-01-04T13:48:14Z Power quality enhancement using active power filter five-level cascade H-bridge under unbalanced and distorted grid Power quality enhancement using active power filter five-level cascade H-bridge under unbalanced and distorted grid Guergah, M. Nebti, K. Rezgui, S. E. Benalla, H. Ould-Abdeslam, D. multilevel active power filter total harmonic distortion instantaneous active and reactive power harmonic currents synchronous reference frame theory багаторівневий фільтр активної потужності повні гармонічні спотворення миттєва активна та реактивна потужності гармонічні струми синхронна теорія системи відліку Introduction. To improve the power quality of a supply system, the total harmonic distortion (THD) is the most important parameter in the quantification of harmonics caused by nonlinear loads. In practice, it must be less than 5 %. The novelty of the proposed work consists in the use of a cascaded five level active filter, when the converter consisting of six H-bridge pairs, each one includes four transistors. Purpose. To increase the efficiency of this filter, two techniques for quantification of harmonic currents are proposed, first the PQ-theory which is simple but can only be used in case of a balanced grid, and second the synchronous reference frame theory (SFR-theory), which is capable of creating harmonic current not only in an unbalanced grid, but also in an unbalanced and distorted beam. Methods. Using the control techniques, the harmonic current is extracted from load current and considered as a reference. The constructed current should follow this reference. Results. The estimation of the active and reactive powers is based on the measurement of the currents crossing the load and the network voltages, these powers are used to determine the shape of the harmonic (reference) current. Using the PI regulator, the output current of the five-level inverter follows the reference current perfectly. The inverters output current is injected into the grid to eliminate harmonic currents. Practical value. In practice, the harmonic distortion rate THD is the most widely used criterion for criticizing the waveform of the currents and judging the quality of the energy involved. For currents on the source side, the THD is considered acceptable if it is less than 5 %, in our proposal the THD is 0.85 % with the PQ-theory and 2.34 % with SFR-theory, so it is optimal. Вступ. Для поліпшення якості електроенергії у системі електропостачання загальне гармонічне спотворення (ЗГС) є найважливішим параметром кількісної оцінки гармонік, викликаних нелінійними навантаженнями. На практиці вона має бути меншою за 5 %. Новизна запропонованої роботи полягає у використанні каскадного п’ятирівневого активного фільтра, коли перетворювач складається з шести пар Н-мостів, кожна з яких включає чотири транзистора. Мета. Щоб підвищити ефективність цього фільтра, пропонуються два методи кількісного визначення гармонійних струмів: по-перше, PQ-теорія, яка проста, але може використовуватися лише у разі збалансованої сітки, і, по-друге, теорія синхронної системи відліку (теорія SFR). , який здатний створювати гармонійний струм не тільки в несиметричній сітці, а й у несиметричному та спотвореному пучку. Методи. Використовуючи методи управління, гармонійний струм витягується зі струму навантаження і розглядається як опорний. Побудований струм повинен слідувати за цим посиланням. Результати. Оцінка активної та реактивної потужностей заснована на вимірюванні струмів, що проходять через навантаження, та мережевих напруг, за цими потужностями визначається форма гармонійного (опорного) струму. При використанні ПІ-регулятора вихідний струм п’ятирівневого інвертора точно відповідає опорному струму. Вихідний струм інвертора подається до мережі для усунення гармонійних струмів. Практична цінність. Насправді коефіцієнт гармонійних спотворень ЗГС є найбільш широко використовуваним критерієм для критики форми хвилі струмів та оцінки якості задіяної енергії. Для струмів на стороні джерела ЗГС вважається прийнятним, якщо він менше 5 %, за нашою пропозицією ЗГС становить 0,85 % з PQ-теорією і 2,34 % з SFR-теорією, тому він є оптимальним. National Technical University "Kharkiv Polytechnic Institute" and State Institution “Institute of Technical Problems of Magnetism of the National Academy of Sciences of Ukraine” 2023-01-04 Article Article application/pdf http://eie.khpi.edu.ua/article/view/257421 10.20998/2074-272X.2023.1.03 Electrical Engineering & Electromechanics; No. 1 (2023); 20-24 Электротехника и Электромеханика; № 1 (2023); 20-24 Електротехніка і Електромеханіка; № 1 (2023); 20-24 2309-3404 2074-272X en http://eie.khpi.edu.ua/article/view/257421/266655 Copyright (c) 2022 M. Guergah, K. Nebti, S. E. Rezgui, H. Benalla, D. Ould-Abdeslam http://creativecommons.org/licenses/by-nc/4.0