RESEARCH ON ELECTRIC POTENTIALS ALIGNMENT ON THE GROUND SURFACE WITHIN THE GROUNDING CONDUCTOR TERRITORY
Results of research on distribution of electric potentials on the earth surface in the territory with a grounding conductor are analyzed. It is shown that potential over the center of a square grounding conductor can be higher than that over the electrode. It is suggested to estimate the limit size...
Збережено в:
| Дата: | 2014 |
|---|---|
| Автори: | , , |
| Формат: | Стаття |
| Мова: | Russian |
| Опубліковано: |
National Technical University "Kharkiv Polytechnic Institute" and Аnatolii Pidhornyi Institute of Power Machines and Systems of NAS of Ukraine
2014
|
| Теми: | |
| Онлайн доступ: | http://eie.khpi.edu.ua/article/view/2074-272X.2014.4.14 |
| Теги: |
Додати тег
Немає тегів, Будьте першим, хто поставить тег для цього запису!
|
| Назва журналу: | Electrical Engineering & Electromechanics |
Репозитарії
Electrical Engineering & Electromechanics| Резюме: | Results of research on distribution of electric potentials on the earth surface in the territory with a grounding conductor are analyzed. It is shown that potential over the center of a square grounding conductor can be higher than that over the electrode. It is suggested to estimate the limit size of the cell of a complex net grounding conductor depending on the depth of its laying. It is found that a two-level design of the grounding conductor reduces touch voltage. Novelty of the results consists in application of a mathematical model to investigating electric characteristics of a two-level grounding conductor versus its laying depth. |
|---|