Analytical solution of conductor tensile force in asymmetrical spans used in overhead power lines and substations with influence of tension insulators

Introduction. Designing electrical substations involves analyzing the horizontal tensile force in flexible tension conductors under varying temperatures. These temperature changes affect the conductor’s length and forces. Problem. Existing methods for calculating horizontal tensile force in conducto...

Повний опис

Збережено в:
Бібліографічні деталі
Дата:2024
Автори: Bendik, J., Cenky, M., Paulech, J., Goga, V.
Формат: Стаття
Мова:English
Опубліковано: National Technical University "Kharkiv Polytechnic Institute" and State Institution “Institute of Technical Problems of Magnetism of the National Academy of Sciences of Ukraine” 2024
Теми:
Онлайн доступ:http://eie.khpi.edu.ua/article/view/305200
Теги: Додати тег
Немає тегів, Будьте першим, хто поставить тег для цього запису!
Назва журналу:Electrical Engineering & Electromechanics

Репозитарії

Electrical Engineering & Electromechanics
id eiekhpieduua-article-305200
record_format ojs
institution Electrical Engineering & Electromechanics
baseUrl_str
datestamp_date 2024-08-19T17:45:12Z
collection OJS
language English
topic substation
asymmetrical span
tension section
state change
підстанція
несиметричний проліт
натяжна ділянка
зміна стану
spellingShingle substation
asymmetrical span
tension section
state change
підстанція
несиметричний проліт
натяжна ділянка
зміна стану
Bendik, J.
Cenky, M.
Paulech, J.
Goga, V.
Analytical solution of conductor tensile force in asymmetrical spans used in overhead power lines and substations with influence of tension insulators
topic_facet substation
asymmetrical span
tension section
state change
підстанція
несиметричний проліт
натяжна ділянка
зміна стану
format Article
author Bendik, J.
Cenky, M.
Paulech, J.
Goga, V.
author_facet Bendik, J.
Cenky, M.
Paulech, J.
Goga, V.
author_sort Bendik, J.
title Analytical solution of conductor tensile force in asymmetrical spans used in overhead power lines and substations with influence of tension insulators
title_short Analytical solution of conductor tensile force in asymmetrical spans used in overhead power lines and substations with influence of tension insulators
title_full Analytical solution of conductor tensile force in asymmetrical spans used in overhead power lines and substations with influence of tension insulators
title_fullStr Analytical solution of conductor tensile force in asymmetrical spans used in overhead power lines and substations with influence of tension insulators
title_full_unstemmed Analytical solution of conductor tensile force in asymmetrical spans used in overhead power lines and substations with influence of tension insulators
title_sort analytical solution of conductor tensile force in asymmetrical spans used in overhead power lines and substations with influence of tension insulators
title_alt Analytical solution of conductor tensile force in asymmetrical spans used in overhead power lines and substations with influence of tension insulators
description Introduction. Designing electrical substations involves analyzing the horizontal tensile force in flexible tension conductors under varying temperatures. These temperature changes affect the conductor’s length and forces. Problem. Existing methods for calculating horizontal tensile force in conductors often focus on symmetric spans or require complex finite element modeling (FEM), which is impractical for routine substation design. Asymmetric spans with tension insulators present a more complex challenge that current solutions do not adequately address. Purpose. Universal analytical solution and algorithm for calculating the horizontal tensile forces in conductors in asymmetric spans with tension insulators used in power substations or short overhead power line spans. The solution is designed to be easily implementable in software without requiring complex tools or extensive FEM. Methodology. The methodology involves deriving an analytical solution based on the catenary curve formed by the conductor between attachment points at different heights. The analysis includes calculating the conductor’s length for a given tensile force and using a state change equation to determine forces under new temperature conditions. Validation is performed using FEM calculations. Results. The proposed solution was validated against FEM models with varying height differences (5 m and 15 m) and conductor temperatures (–30 °C, –5 °C, +80 °C). The results showed a minimal error (less than 0.15 %) between the analytical solution and FEM results, demonstrating high accuracy. Originality. This paper presents a novel analytical solution to the problem of calculating tensile forces in asymmetric spans with tension insulators. Unlike existing methods, our solution is straightforward and easily implementable in any programming language. Practical value. The solution is practical for routine design tasks in electrical substations or short overhead power lines. Especially in power substations, accurate tensile forces are needed not only for mechanical design and sag calculations but also for calculating the dynamic effects of short-circuit currents. References 23, tables 4, figures 3.
publisher National Technical University "Kharkiv Polytechnic Institute" and State Institution “Institute of Technical Problems of Magnetism of the National Academy of Sciences of Ukraine”
publishDate 2024
url http://eie.khpi.edu.ua/article/view/305200
work_keys_str_mv AT bendikj analyticalsolutionofconductortensileforceinasymmetricalspansusedinoverheadpowerlinesandsubstationswithinfluenceoftensioninsulators
AT cenkym analyticalsolutionofconductortensileforceinasymmetricalspansusedinoverheadpowerlinesandsubstationswithinfluenceoftensioninsulators
AT paulechj analyticalsolutionofconductortensileforceinasymmetricalspansusedinoverheadpowerlinesandsubstationswithinfluenceoftensioninsulators
AT gogav analyticalsolutionofconductortensileforceinasymmetricalspansusedinoverheadpowerlinesandsubstationswithinfluenceoftensioninsulators
first_indexed 2024-08-20T04:03:31Z
last_indexed 2024-08-20T04:03:31Z
_version_ 1811501853969481728
spelling eiekhpieduua-article-3052002024-08-19T17:45:12Z Analytical solution of conductor tensile force in asymmetrical spans used in overhead power lines and substations with influence of tension insulators Analytical solution of conductor tensile force in asymmetrical spans used in overhead power lines and substations with influence of tension insulators Bendik, J. Cenky, M. Paulech, J. Goga, V. substation asymmetrical span tension section state change підстанція несиметричний проліт натяжна ділянка зміна стану Introduction. Designing electrical substations involves analyzing the horizontal tensile force in flexible tension conductors under varying temperatures. These temperature changes affect the conductor’s length and forces. Problem. Existing methods for calculating horizontal tensile force in conductors often focus on symmetric spans or require complex finite element modeling (FEM), which is impractical for routine substation design. Asymmetric spans with tension insulators present a more complex challenge that current solutions do not adequately address. Purpose. Universal analytical solution and algorithm for calculating the horizontal tensile forces in conductors in asymmetric spans with tension insulators used in power substations or short overhead power line spans. The solution is designed to be easily implementable in software without requiring complex tools or extensive FEM. Methodology. The methodology involves deriving an analytical solution based on the catenary curve formed by the conductor between attachment points at different heights. The analysis includes calculating the conductor’s length for a given tensile force and using a state change equation to determine forces under new temperature conditions. Validation is performed using FEM calculations. Results. The proposed solution was validated against FEM models with varying height differences (5 m and 15 m) and conductor temperatures (–30 °C, –5 °C, +80 °C). The results showed a minimal error (less than 0.15 %) between the analytical solution and FEM results, demonstrating high accuracy. Originality. This paper presents a novel analytical solution to the problem of calculating tensile forces in asymmetric spans with tension insulators. Unlike existing methods, our solution is straightforward and easily implementable in any programming language. Practical value. The solution is practical for routine design tasks in electrical substations or short overhead power lines. Especially in power substations, accurate tensile forces are needed not only for mechanical design and sag calculations but also for calculating the dynamic effects of short-circuit currents. References 23, tables 4, figures 3. Вступ. Проєктування електричних підстанцій включає аналіз горизонтальної сили, що розтягує, в гнучких натяжних провідниках при різних температурах. Ці зміни температури впливають на довжину провідника та сили. Проблема. Існуючі методи розрахунку горизонтальної сили, що розтягує, у провідниках часто орієнтовані на симетричні прольоти або вимагають складного моделювання методом скінченних елементів (FEM), що непрактично для звичайного проєктування підстанцій. Асиметричні прольоти з натяжними ізоляторами є складнішим завданням, яке існуючі рішення не вирішують належним чином. Мета. Універсальне аналітичне рішення та алгоритм розрахунку горизонтальних сил, що розтягують, у проводах несиметричних прольотів з натяжними ізоляторами, що застосовуються на силових підстанціях або коротких прольотах повітряних ліній електропередачі. Рішення розроблено таким чином, щоб його можна було легко реалізувати в програмному забезпеченні, не вимагаючи складних інструментів або моделювання методом FEM. Методика передбачає отримання аналітичного рішення на основі контактної кривої, утвореної провідником між точками кріплення на різній висоті. Аналіз включає розрахунок довжини провідника для заданої розтягуючої сили і використання рівняння зміни стану для визначення сил в нових температурних умовах. Перевірка здійснюється з використанням розрахунків методом FEM. Результати. Запропоноване рішення було перевірено на моделях FEM з різною різницею висот (5 м та 15 м) та температурою провідника (–30 °C, –5 °C, +80 °C). Результати показали мінімальну помилку (менше 0,15 %) між аналітичним рішенням та результатами FEM, демонструючи високу точність. Оригінальність. У цій статті представлено нове аналітичне рішення задачі розрахунку зусиль, що розтягують, у несиметричних прольотах з натяжними ізоляторами. На відміну від існуючих методів, наше рішення є простим та легко реалізованим будь-якою мовою програмування. Практична цінність. Вирішення практично для рутинних завдань проєктування електричних підстанцій або коротких повітряних ліній електропередачі. Точні сили, що розтягують, необхідні, особливо на силових підстанціях, не тільки для механічного проєктування та розрахунку провисання, але і для розрахунку динамічних ефектів струмів короткого замикання. Бібл. 23, табл. 4, рис. 3. National Technical University "Kharkiv Polytechnic Institute" and State Institution “Institute of Technical Problems of Magnetism of the National Academy of Sciences of Ukraine” 2024-08-19 Article Article application/pdf http://eie.khpi.edu.ua/article/view/305200 10.20998/2074-272X.2024.5.09 Electrical Engineering & Electromechanics; No. 5 (2024); 64-69 Электротехника и Электромеханика; № 5 (2024); 64-69 Електротехніка і Електромеханіка; № 5 (2024); 64-69 2309-3404 2074-272X en http://eie.khpi.edu.ua/article/view/305200/300588 Copyright (c) 2024 J. Bendik, M. Cenky, J. Paulech, V. Goga http://creativecommons.org/licenses/by-nc/4.0