THE EXPERIMENTAL VALIDATION OF THE GROUNDING DEVICE RESISTANCE MEASUREMENT METHOD

Purpose. The paper considers experimental research of three-electrode units for measuring the resistance of grounding devices for different purposes. Methodology. The experimental study of the method of resistance measurement of grounding devices for any design in any soil structure using the method...

Full description

Saved in:
Bibliographic Details
Main Authors: Nizhevskyi, I. V., Nizhevskyi, V. I., Bondarenko, V. E.
Format: Article
Language:English
Russian
Published: National Technical University "Kharkiv Polytechnic Institute" and State Institution “Institute of Technical Problems of Magnetism of the National Academy of Sciences of Ukraine” 2016
Subjects:
Online Access:http://eie.khpi.edu.ua/article/view/2074-272X.2016.6.10
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:Purpose. The paper considers experimental research of three-electrode units for measuring the resistance of grounding devices for different purposes. Methodology. The experimental study of the method of resistance measurement of grounding devices for any design in any soil structure using the method of physical modeling is presented. Results. By results of model operation the set of equations of the sixth order is solved. It allowed to determine the own and mutual impedance in the three-electrode unit with high accuracy without searching the point of zero potential. Features of measuring and defining the own and relative resistances of various combinations of electrodes for three-electrode measuring unit are considered. Originality. The necessity of finding a zero potential point is excluded. Practical value. The proposed method provides the smallest possible spacing of potential electrodes outside the grounding devices. This reduces the wiring length measurement circuit in several times, increases the ratio «signal – noise», removes the restrictions on building of the territory outside the test grounding device.