THE EXPERIMENTAL VALIDATION OF THE GROUNDING DEVICE RESISTANCE MEASUREMENT METHOD

Purpose. The paper considers experimental research of three-electrode units for measuring the resistance of grounding devices for different purposes. Methodology. The experimental study of the method of resistance measurement of grounding devices for any design in any soil structure using the method...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Datum:2016
Hauptverfasser: Nizhevskyi, I. V., Nizhevskyi, V. I., Bondarenko, V. E.
Format: Artikel
Sprache:English
Russian
Veröffentlicht: National Technical University "Kharkiv Polytechnic Institute" and Аnatolii Pidhornyi Institute of Power Machines and Systems of NAS of Ukraine 2016
Schlagworte:
Online Zugang:http://eie.khpi.edu.ua/article/view/2074-272X.2016.6.10
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Назва журналу:Electrical Engineering & Electromechanics

Institution

Electrical Engineering & Electromechanics
Beschreibung
Zusammenfassung:Purpose. The paper considers experimental research of three-electrode units for measuring the resistance of grounding devices for different purposes. Methodology. The experimental study of the method of resistance measurement of grounding devices for any design in any soil structure using the method of physical modeling is presented. Results. By results of model operation the set of equations of the sixth order is solved. It allowed to determine the own and mutual impedance in the three-electrode unit with high accuracy without searching the point of zero potential. Features of measuring and defining the own and relative resistances of various combinations of electrodes for three-electrode measuring unit are considered. Originality. The necessity of finding a zero potential point is excluded. Practical value. The proposed method provides the smallest possible spacing of potential electrodes outside the grounding devices. This reduces the wiring length measurement circuit in several times, increases the ratio «signal – noise», removes the restrictions on building of the territory outside the test grounding device.