ОПТИМАЛЬНИЙ РОЗПОДІЛ РЕАКТИВНОЇ ПОТУЖНОСТІ МІЖ СИНХРОННИМИ І АСИНХРОНІЗОВАНИМИ ТУРБОГЕНЕРАТОРАМИ

Based on the Lagrange multiplier method, methodology, mathematical and digital models of optimal var dispatch between synchronous and asynchronized (synchronous operation) turbo generators at TPS were developed; these take into account the influence of generator transformers and auxiliary service tr...

Full description

Saved in:
Bibliographic Details
Date:2012
Main Authors: Сегеда, М.С., Олексин, В.П., Олексин, А.В.
Format: Article
Language:Ukrainian
Published: Інститут електродинаміки НАН України, Київ 2012
Subjects:
Online Access:https://techned.org.ua/index.php/techned/article/view/1374
Tags: Add Tag
No Tags, Be the first to tag this record!
Journal Title:Technical Electrodynamics

Institution

Technical Electrodynamics
Description
Summary:Based on the Lagrange multiplier method, methodology, mathematical and digital models of optimal var dispatch between synchronous and asynchronized (synchronous operation) turbo generators at TPS were developed; these take into account the influence of generator transformers and auxiliary service transformers, as well as secure the active power minimum losses. It was determined that generators reactive power optimum values depend on their types, their active load, generator transformers and auxiliary service transformers parameters, and the unit auxiliaries power circuit. References 10, figures 2.