ЗАСТОСУВАННЯ УМОВНО ДВАНАДЦЯТИФАЗНОГО КЕРОВАНОГО КОМПЕНСАЦІЙНОГО ПЕРЕТВОРЮВАЧА ДЛЯ ПОСЛІДОВНОГО ПРЯМОГО ЗАПУСКУ ВІД ЕЛЕКТРИЧНОЇ МЕРЕЖІ ЧОТИРЬОХ ПОТУЖНИХ АСИНХРОННИХ МАШИН
The sequential direct start-up of four asynchronous machines (AM) with a capacity of 8 MW each from a 6 kV electrical network is considered. The start-up transient modes that arise in the network as a result of such an AM start-up are investigated, as well as the possible consequences for the networ...
Saved in:
| Date: | 2024 |
|---|---|
| Main Authors: | , |
| Format: | Article |
| Language: | Ukrainian |
| Published: |
Інститут електродинаміки НАН України, Київ
2024
|
| Subjects: | |
| Online Access: | https://techned.org.ua/index.php/techned/article/view/1648 |
| Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
| Journal Title: | Technical Electrodynamics |
Institution
Technical Electrodynamics| Summary: | The sequential direct start-up of four asynchronous machines (AM) with a capacity of 8 MW each from a 6 kV electrical network is considered. The start-up transient modes that arise in the network as a result of such an AM start-up are investigated, as well as the possible consequences for the network. To facilitate the direct start of AM with a capacity of 8 MW, it is proposed to use a conditional twelve-phase controlled compensating converter, which limits the amount of starting overcurrents in the network. References 10, figures 6. |
|---|