ВИЗНАЧЕННЯ ВЕЛИЧИНИ ЄМНОСТІ СИСТЕМИ ПРОВІД-ІЗОЛЯТОР-ШТИР В ПОВІТРЯНИХ ЛІНІЯХ НАПРУГОЮ 6-10 кВ ДЛЯ ОЦІНКИ МОЖЛИВОСТІ РАННЬОЇ ДІАГНОСТИКИ СТАНУ ІЗОЛЯЦІЇ

The negative influence of single-phase-to-ground faults in networks with an isolated neutral, resulting from a breakdown of pin insulation, is analyzed. A concept for early detection of damage to pin insulators is proposed, based on measuring changes in leakage current through the insulators caused...

Повний опис

Збережено в:
Бібліографічні деталі
Дата:2024
Автори: Буйний, Р.О., Безручко, В.М., Строгій, А.Ю.
Формат: Стаття
Мова:Ukrainian
Опубліковано: Інститут електродинаміки НАН України, Київ 2024
Теми:
Онлайн доступ:https://techned.org.ua/index.php/techned/article/view/1661
Теги: Додати тег
Немає тегів, Будьте першим, хто поставить тег для цього запису!
Назва журналу:Technical Electrodynamics

Репозитарії

Technical Electrodynamics
Опис
Резюме:The negative influence of single-phase-to-ground faults in networks with an isolated neutral, resulting from a breakdown of pin insulation, is analyzed. A concept for early detection of damage to pin insulators is proposed, based on measuring changes in leakage current through the insulators caused by changes in the capacitance of the “pin-insulator-wire” system. For this purpose, a simulation of the system was done. A model of the geometric dimensions of the insulator is created with taking into account the design features of the installation of the line wire in the AutoCAD software package and the distribution of the electric field is simulated in the Comsol Multiphysics 5.6 package, which makes it possible to estimate the electrical capacitance. The dependence of the calculated electrical capacitance of ShF-20G insulators on the dielectric constant, diameters and grades of wires used on 6-10 kV overhead power lines and options for wire bundles is considered. Numerical values of the capacitance of the “pin-insulator-wire” system were obtained for different configuration options. It has been shown that the state of the insulator material has a decisive influence on the capacity of the system. References 11, figures 2, tables 2.