БЕЗПЕЧНЕ ВІДКЛЮЧЕННЯ ЕЛЕГАЗОВИХ ВИМИКАЧАІВ У ПОВІТРЯНИХ ЛІНІЯХ ЕЛЕКТРОПЕРЕДАЧІ

The paper analyses the transient currents during the energisation of a 750 kV overhead transmission line (OTL). The safety of OTL state after symmetrical and asymmetrical closing of the circuit breakers and technical feasibility of SF6 circuit breakers opening with time delay after their closing is...

Full description

Saved in:
Bibliographic Details
Date:2021
Main Author: Шполянський, О.Г.
Format: Article
Language:Ukrainian
Published: Інститут електродинаміки НАН України, Київ 2021
Subjects:
Online Access:https://techned.org.ua/index.php/techned/article/view/187
Tags: Add Tag
No Tags, Be the first to tag this record!
Journal Title:Technical Electrodynamics

Institution

Technical Electrodynamics
Description
Summary:The paper analyses the transient currents during the energisation of a 750 kV overhead transmission line (OTL). The safety of OTL state after symmetrical and asymmetrical closing of the circuit breakers and technical feasibility of SF6 circuit breakers opening with time delay after their closing is substantiated. The necessity of transient processes simulation for analysing the characteristics of periodic and direct components of currents is shown. A method for determining of SF6 circuit breaker opening time delay for a set of states that may arise after the energisation of OTL is developed. References 13, tables 2, figures 5.