ВИЗНАЧЕННЯ МІСЦЯ ОДНОФАЗНОГО ЗАМИКАННЯ НА ЗЕМЛЮ В УМОВАХ ЕЛЕКТРОМАГНІТНОГО ВПЛИВУ НА ПОВІТРЯНІ ЛІНІЇ СИГНАЛІЗАЦІЇ, ЦЕНТРАЛІЗАЦІЇ ТА БЛОКУВАННЯ ЗАЛІЗНИЦЬ
The analysis of the influence factors on the accuracy of the location of the earth fault on an overhead line with a distributed load The existence of an inverse dependence of the value of the first harmonic part in the voltage of the damaged phase from the distance to the closure is theoretically su...
Gespeichert in:
| Datum: | 2019 |
|---|---|
| Hauptverfasser: | , , , |
| Format: | Artikel |
| Sprache: | Ukrainian |
| Veröffentlicht: |
Інститут електродинаміки НАН України, Київ
2019
|
| Schlagworte: | |
| Online Zugang: | https://techned.org.ua/index.php/techned/article/view/482 |
| Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
| Назва журналу: | Technical Electrodynamics |
Institution
Technical Electrodynamics| Zusammenfassung: | The analysis of the influence factors on the accuracy of the location of the earth fault on an overhead line with a distributed load The existence of an inverse dependence of the value of the first harmonic part in the voltage of the damaged phase from the distance to the closure is theoretically substantiated and experimentally confirmed. One of the main reasons for this is the distributed along the line load, which is connected to the line through single-phase transformers. Proposed measures to improve the quality of the electric energy of the line and the accuracy of the determination of the location of the closure. References 9, figures 5. |
|---|