ОБҐРУНТУВАННЯ ОБЛАСТІ ВИКОРИСТАННЯ КЛАСУ НАПРУГИ 20 КВ У МІСЬКИХ ЕЛЕКТРИЧНИХ МЕРЕЖАХ УКРАЇНИ
For biradial power supply networks it was derived an objective function that allows to analyze the effect of technological and economic factors on the efficiency of power supply. It was found that utilizing the voltage class of 20 kV in the urban power supply networks would be efficient only when th...
Gespeichert in:
| Datum: | 2019 |
|---|---|
| Hauptverfasser: | , , , |
| Format: | Artikel |
| Sprache: | Ukrainian |
| Veröffentlicht: |
Інститут електродинаміки НАН України, Київ
2019
|
| Schlagworte: | |
| Online Zugang: | https://techned.org.ua/index.php/techned/article/view/494 |
| Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
| Назва журналу: | Technical Electrodynamics |
Institution
Technical Electrodynamics| Zusammenfassung: | For biradial power supply networks it was derived an objective function that allows to analyze the effect of technological and economic factors on the efficiency of power supply. It was found that utilizing the voltage class of 20 kV in the urban power supply networks would be efficient only when they are constructed with transformers of unit capacity630 kVA and aluminum cables of 240 mm2 or larger cross-section. Analytic expressions were derived and visualizations were created to analyze minimal specific density of electric load and maximum distance between electric substations for which construction of power supply network of 20 kV is justified as a function of allowed outage time for the network. References 6, figures 3. |
|---|