АНАЛІЗ ЗМІНИ ЧАСТОТИ В ОЕС УКРАЇНИ ЗА УМОВ ВІДКЛЮЧЕННЯ ЕНЕРГОБЛОКА АТОМНОЇ ЕЛЕКТРОСТАНЦІЇ

The current state of the primary and automatic secondary frequency control in the interconnected power system (IPS) of Ukraine has been considered. A quality analysis of the load-frequency control in IPS of Ukraine has been performed in the event of a disconnection of 1,000 MW generating unit at the...

Full description

Saved in:
Bibliographic Details
Date:2022
Main Authors: Павловський, В.В., Стелюк, А.О., Лук'яненко, Л.М., Леньга, О.В.
Format: Article
Language:Ukrainian
Published: Інститут електродинаміки НАН України, Київ 2022
Subjects:
Online Access:https://techned.org.ua/index.php/techned/article/view/653
Tags: Add Tag
No Tags, Be the first to tag this record!
Journal Title:Technical Electrodynamics

Institution

Technical Electrodynamics
Description
Summary:The current state of the primary and automatic secondary frequency control in the interconnected power system (IPS) of Ukraine has been considered. A quality analysis of the load-frequency control in IPS of Ukraine has been performed in the event of a disconnection of 1,000 MW generating unit at the nuclear power plant. The stiffness coefficients of IPS of Ukraine, the unified power system (UPS) of Russia in case of their joint operation have been determined and an estimation of the load-frequency control in IPS of Ukraine by using "trumpet curves" has been performed as well. It is established that despite the unimproved organization of the load-frequency control in such conditions, the frequency control is maintained in IPS of Ukraine. References 6, figures 5.