The article presents comparative identification results of low-frequency components of the signals in the cases of using their both effective and instantaneous values. It is shown that using of instantaneous values of power system operational condition parameters measured by phasor measurement units...

Full description

Saved in:
Bibliographic Details
Date:2017
Main Authors: Буткевич, О.Ф., Чижевський, В.В.
Format: Article
Language:Ukrainian
Published: Інститут електродинаміки НАН України, Київ 2017
Subjects:
Online Access:https://techned.org.ua/index.php/techned/article/view/759
Tags: Add Tag
No Tags, Be the first to tag this record!
Journal Title:Technical Electrodynamics

Institution

Technical Electrodynamics
Description
Summary:The article presents comparative identification results of low-frequency components of the signals in the cases of using their both effective and instantaneous values. It is shown that using of instantaneous values of power system operational condition parameters measured by phasor measurement units will increase a detection reliability of low-frequency modes of electromechanical oscillations, however, such use in real time will require a high processor speed. Therefore, for reliable detection of low-frequency modes it is more expedient to increase the observation window’s width and to use the effective values of the power system operational condition parameters. References 10, tables 3, figures 6.