РОЗПОДІЛ ЕЛЕКТРИЧНОГО ПОЛЯ В МУФТІ СИЛОВОГО КАБЕЛЯ СЕРЕДНЬОЇ НАПРУГИ З УРАХУВАННЯМ ЗОВНІШНЬОГО НАПІВПРОВІДНОГО ПОКРИТТЯ ЙОГО ПОЛІЕТИЛЕНОВОЇ ІЗОЛЯЦІЇ
The computer modeling of electric field in the termination of medium-voltage (10 kV) cross-linked polyethylene insulated power cable is carried out. The stress-control tube and mastic are used in the termination to reduce the field nonuniformity. The electric field distributions are examined at diff...
Gespeichert in:
| Datum: | 2016 |
|---|---|
| 1. Verfasser: | |
| Format: | Artikel |
| Sprache: | English |
| Veröffentlicht: |
Інститут електродинаміки НАН України, Київ
2016
|
| Schlagworte: | |
| Online Zugang: | https://techned.org.ua/index.php/techned/article/view/783 |
| Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
| Назва журналу: | Technical Electrodynamics |
Institution
Technical Electrodynamics| Zusammenfassung: | The computer modeling of electric field in the termination of medium-voltage (10 kV) cross-linked polyethylene insulated power cable is carried out. The stress-control tube and mastic are used in the termination to reduce the field nonuniformity. The electric field distributions are examined at different stress control tube positions relative to the cutting ends of the cable outer semiconducting layer and copper wire shield. The properties of stress control tube and mastic are varied to determine their influence on maximum electric intensity in the cable insulation. The results and used approaches to the study of electric field can be applied to design the terminations allowing for the appropriate materials and arrangement of structural parts. References 11, figures 5, table 1. |
|---|