ВИЗНАЧЕННЯ РАЦІОНАЛЬНИХ МІСЦЬ ВСТАНОВЛЕННЯ АВТОМАТИЧНИХ СЕКЦІОНУЮЧИХ РОЗ'ЄДНУВАЧІВ В РОЗПОДІЛЬНИХ МЕРЕЖАХ НАПРУГОЮ 10 КВ

The methodology for selection of rational installation location of partitioning switching devices, namely disconnectors of a new generation RLK-10, RLN-10 with autolink ABB has been proposed in this work. It is shown that for selection of rational installation location of such partitioning switching...

Full description

Saved in:
Bibliographic Details
Date:2014
Main Author: Діхтярук , І.В.
Format: Article
Language:Ukrainian
Published: Інститут електродинаміки НАН України, Київ 2014
Subjects:
Online Access:https://techned.org.ua/index.php/techned/article/view/1070
Tags: Add Tag
No Tags, Be the first to tag this record!
Journal Title:Technical Electrodynamics

Institution

Technical Electrodynamics
Description
Summary:The methodology for selection of rational installation location of partitioning switching devices, namely disconnectors of a new generation RLK-10, RLN-10 with autolink ABB has been proposed in this work. It is shown that for selection of rational installation location of such partitioning switching devices the distribution networks with the voltage of 6–10 kV of any configuration, you can use the objective function – reduction undersupply of electricity to consumers. By bringing the distribution function of consumer along the transmission line to the linear, logarithmic or exponential form, was obtained rational installation location sektsionuyuchyh disconnectors. For the case of uniform power distribution along the length of the line was obtained efficient installation location disconnector, which is 64% of the total length of the line. References 5, figures 4.