АНАЛІЗ ЕЛЕКТРОМАГНІТНИХ ПРОЦЕСІВ В КОЛІ «ОБМЕЖУВАЧ НАПРУГИ – ФІЛЬТР НИЖНІХ ЧАСТОТ» ЗА ДІЇ ВИСОКОВОЛЬТНОЇ ІМПУЛЬСНОЇ ЗАВАДИ З МЕРЕЖІ ЕЛЕКТРОЖИВЛЕННЯ

In the work, a theoretical analysis of high-voltage surge (HVS) passing from a power supply network through the path "voltage limiter - low-pass filter" is carried out, with the aim to evaluate the effectiveness of the filter on reducing the amplitude of the residual HVS at the input of el...

Full description

Saved in:
Bibliographic Details
Date:2023
Main Authors: Павловський, В.О., Гурін, В.К., Юрченко, О.М.
Format: Article
Language:Ukrainian
Published: Інститут електродинаміки НАН України, Київ 2023
Subjects:
Online Access:https://techned.org.ua/index.php/techned/article/view/1488
Tags: Add Tag
No Tags, Be the first to tag this record!
Journal Title:Technical Electrodynamics

Institution

Technical Electrodynamics
Description
Summary:In the work, a theoretical analysis of high-voltage surge (HVS) passing from a power supply network through the path "voltage limiter - low-pass filter" is carried out, with the aim to evaluate the effectiveness of the filter on reducing the amplitude of the residual HVS at the input of electrical and/or radio-electronic equipment. As a low-pass filter (LPF), an L-shaped filter was chosen. Typical means of limiting the amplitude of the HVS (gas-filled arresters, varistors, and suppressors) are analyzed, and their shortcomings are shown. The justification of the equivalent scheme for theoretical analysis is given. The analysis revealed a direct relationship between the cut-off frequency of the LPF, which is determined by the nominal values of its elements, and the amplitude of the residual HVS at the mains input of the equipment, and also showed the effectiveness of inserting the LPF between the output of a typical HVS voltage limiter and the mains input of the mentioned equipment from the point of view of additional reduction of the residual HVS amplitude. References 18, figures 6.