ДОСЛІДЖЕННЯ АЛГОРИТМУ ЗАХИСТУ, ЩО ДІЄ НА ОСНОВІ ДИФЕРЕНЦІАЛА ІМПЕДАНСУ ДЛЯ ЗОВНІШНІХ КЗ, З ВРАХУВАННЯМ НАСИЧЕННЯ ТРАНСФОРМАТОРА СТРУМУ
In this paper, the analysis of impedance - differential protective algorithm dedicated for transmission line protection relay is presented. Measurements of current and voltage at both line ends enable to formulate a differential impedance which constitutes efficient criterion for protection purposes...
Gespeichert in:
| Datum: | 2018 |
|---|---|
| Hauptverfasser: | , , |
| Format: | Artikel |
| Sprache: | English |
| Veröffentlicht: |
Інститут електродинаміки НАН України, Київ
2018
|
| Schlagworte: | |
| Online Zugang: | https://techned.org.ua/index.php/techned/article/view/682 |
| Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
| Назва журналу: | Technical Electrodynamics |
Institution
Technical Electrodynamics| Zusammenfassung: | In this paper, the analysis of impedance - differential protective algorithm dedicated for transmission line protection relay is presented. Measurements of current and voltage at both line ends enable to formulate a differential impedance which constitutes efficient criterion for protection purposes. Special attention is focused on algorithm operation in case of external faults appearance, which have to be distinguished properly due to security reasons in both situations - without and with CTs saturation. The sensitivity and the reliability of the presented protection algorithm were evaluated based on simulation carried out in ATP-EMTP simulation program. References 9, tables 1, figures 3. |
|---|