ДОСЛІДЖЕННЯ АЛГОРИТМУ ЗАХИСТУ, ЩО ДІЄ НА ОСНОВІ ДИФЕРЕНЦІАЛА ІМПЕДАНСУ ДЛЯ ЗОВНІШНІХ КЗ, З ВРАХУВАННЯМ НАСИЧЕННЯ ТРАНСФОРМАТОРА СТРУМУ

In this paper, the analysis of impedance - differential protective algorithm dedicated for transmission line protection relay is presented. Measurements of current and voltage at both line ends enable to formulate a differential impedance which constitutes efficient criterion for protection purposes...

Full description

Saved in:
Bibliographic Details
Date:2018
Main Authors: Герлендер, Ю., Соляк, К., Іжиковскі, Я.
Format: Article
Language:English
Published: Інститут електродинаміки НАН України, Київ 2018
Subjects:
Online Access:https://techned.org.ua/index.php/techned/article/view/682
Tags: Add Tag
No Tags, Be the first to tag this record!
Journal Title:Technical Electrodynamics

Institution

Technical Electrodynamics
Description
Summary:In this paper, the analysis of impedance - differential protective algorithm dedicated for transmission line protection relay is presented. Measurements of current and voltage at both line ends enable to formulate a differential impedance which constitutes efficient criterion for protection purposes. Special attention is focused on algorithm operation in case of external faults appearance, which have to be distinguished properly due to security reasons in both situations - without and with CTs saturation. The sensitivity and the reliability of the presented protection algorithm were evaluated based on simulation carried out in ATP-EMTP simulation program. References 9, tables 1, figures 3.