ЧАСТОТНАЯ ЗАВИСИМОСТЬ ТАНГЕНСА УГЛА ДИЭЛЕКТРИЧЕСКИХ ПОТЕРЬ ОТ СТЕПЕНИ УВЛАЖНЕНИЯ ПОЛИЭТИЛЕНОВОЙ ИЗОЛЯЦИИ КАБЕЛЕЙ

It is shown that application of the high-frequency relaxation spectroscopy is expedient at the analysis of processes of appearance of free moisture in the polymeric insulation of power cables. The calculated and experimental frequency dependences of dielectric loss tangent on the degree of humidific...

Full description

Saved in:
Bibliographic Details
Date:2016
Main Authors: Беспрозванных , А.В., Кессаев , А.Г., Щерба , М.А.
Format: Article
Language:Ukrainian
Published: Інститут електродинаміки НАН України, Київ 2016
Subjects:
Online Access:https://techned.org.ua/index.php/techned/article/view/784
Tags: Add Tag
No Tags, Be the first to tag this record!
Journal Title:Technical Electrodynamics

Institution

Technical Electrodynamics
Description
Summary:It is shown that application of the high-frequency relaxation spectroscopy is expedient at the analysis of processes of appearance of free moisture in the polymeric insulation of power cables. The calculated and experimental frequency dependences of dielectric loss tangent on the degree of humidification of cable insulation are given. It is revealed that at prolonged moistening of insulation the peaks of relaxation losses are displaced into area of higher frequencies and there are the additional maxima corresponding to dispersion of energy dissipation in the new elements of insulation. The range of change of frequency of relaxation losses depends on concentration of free moisture in insulation and its electro-physical and morphological properties.  References 19, table 1, figure 5.